CVE-2026-2491
Socomec DIRIS A-40 HTTP API Authentication Bypass Vulnerability. This vulnerability allows network-adjacent attackers to bypass authentication on affected installations of Socomec DIRIS A-40 power monitoring devices. Authentication is not required to exploit this vulnerability.
The specific flaw exists within the web API implementation, which listens on TCP port 80 by default. The issue results from the lack of authentication prior to allowing access to functionality. An attacker can leverage this vulnerability to bypass authentication on the system. Was ZDI-CAN-23993.
CVSS
- Versión: 3.0
- Vector: CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L
- Puntuación base: 6.3
Probabilidad de explotación (EPSS)
- Probabilidad de explotación en los próximos 30 días: 0.39%
- Percentil entre todas las CVEs puntuadas: 31
- Fecha de la puntuación: 5/10/2026
EPSS (Exploit Prediction Scoring System, de FIRST) estima la probabilidad de que una vulnerabilidad sea explotada en 30 días. Complementa a CVSS (impacto) y a CISA KEV (explotación confirmada).
Tecnologías afectadas (1)
⚠ Inferidas por IA a partir de la descripción — NVD aún no ha analizado esta CVE; no son CPE verificados.
CWE
- CWE-306
Referencias
JSON original (NVD)
Mostrar
{
"id": "CVE-2026-2491",
"cveTags": [],
"metrics": {
"ssvcV203": [
{
"source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"ssvcData": {
"id": "CVE-2026-2491",
"role": "CISA Coordinator",
"options": [
{
"exploitation": "none"
},
{
"automatable": "no"
},
{
"technicalImpact": "partial"
}
],
"version": "2.0.3",
"timestamp": "2026-03-16T15:26:54.111400Z"
}
}
],
"cvssMetricV30": [
{
"type": "Secondary",
"source": "zdi-disclosures@trendmicro.com",
"cvssData": {
"scope": "UNCHANGED",
"version": "3.0",
"baseScore": 6.3,
"attackVector": "ADJACENT_NETWORK",
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.0/AV:A/AC:L/PR:N/UI:N/S:U/C:L/I:L/A:L",
"integrityImpact": "LOW",
"userInteraction": "NONE",
"attackComplexity": "LOW",
"availabilityImpact": "LOW",
"privilegesRequired": "NONE",
"confidentialityImpact": "LOW"
},
"impactScore": 3.4,
"exploitabilityScore": 2.8
}
]
},
"affected": [
{
"source": "zdi-disclosures@trendmicro.com",
"affectedData": [
{
"vendor": "Socomec",
"product": "DIRIS A-40",
"versions": [
{
"status": "affected",
"version": "1.8.1"
}
],
"defaultStatus": "unknown"
}
]
}
],
"published": "2026-03-16T14:19:30.543",
"references": [
{
"url": "https://emea.socomec.com/en/resource-center/resource-type/cyber-vulnerabilities-601",
"source": "zdi-disclosures@trendmicro.com"
},
{
"url": "https://www.zerodayinitiative.com/advisories/ZDI-26-129/",
"source": "zdi-disclosures@trendmicro.com"
}
],
"vulnStatus": "Awaiting Analysis",
"weaknesses": [
{
"type": "Secondary",
"source": "zdi-disclosures@trendmicro.com",
"description": [
{
"lang": "en",
"value": "CWE-306"
}
]
}
],
"descriptions": [
{
"lang": "en",
"value": "Socomec DIRIS A-40 HTTP API Authentication Bypass Vulnerability. This vulnerability allows network-adjacent attackers to bypass authentication on affected installations of Socomec DIRIS A-40 power monitoring devices. Authentication is not required to exploit this vulnerability.\n\nThe specific flaw exists within the web API implementation, which listens on TCP port 80 by default. The issue results from the lack of authentication prior to allowing access to functionality. An attacker can leverage this vulnerability to bypass authentication on the system. Was ZDI-CAN-23993."
},
{
"lang": "es",
"value": "Vulnerabilidad de omisión de autenticación de la API HTTP de Socomec DIRIS A-40. Esta vulnerabilidad permite a atacantes adyacentes a la red omitir la autenticación en instalaciones afectadas de dispositivos de monitoreo de energía Socomec DIRIS A-40. La autenticación no es necesaria para explotar esta vulnerabilidad.\n\nLa falla específica existe dentro de la implementación de la API web, que escucha en el puerto TCP 80 por defecto. El problema resulta de la falta de autenticación antes de permitir el acceso a la funcionalidad. Un atacante puede aprovechar esta vulnerabilidad para omitir la autenticación en el sistema. Fue ZDI-CAN-23993."
}
],
"lastModified": "2026-06-17T10:31:09.627",
"sourceIdentifier": "zdi-disclosures@trendmicro.com"
}