« Volver al listado

CVE-2025-7693

Estado: AplazadaCrítica (9.3)—

A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault.

CVSS

Probabilidad de explotación (EPSS)

EPSS (Exploit Prediction Scoring System, de FIRST) estima la probabilidad de que una vulnerabilidad sea explotada en 30 días. Complementa a CVSS (impacto) y a CISA KEV (explotación confirmada).

🎯 Técnicas ATT&CK

Cómo se explota esta vulnerabilidad y qué consigue el atacante, en el lenguaje de MITRE ATT&CK.

CIP (red industrial) sin autenticación (PR:N) expuesto en CompactLogix. Packet malformado causa DoS (LED rojo fijo) e inutilización del dispositivo. T1068 secundario por fault state sin recuperación inmediata sin ciclo de potencia.

Inferido por nuestro agente de análisis a partir de la descripción oficial, el vector CVSS y la CWE, y comprobado por un supervisor. Puede contener errores.

🛡️ Mitigaciones ATT&CK que cubren estas técnicas

Tecnologías afectadas (1)

⚠ Inferidas por IA a partir de la descripción — NVD aún no ha analizado esta CVE; no son CPE verificados.

CWE

Referencias

JSON original (NVD)

Mostrar
{
  "id": "CVE-2025-7693",
  "cveTags": [],
  "metrics": {
    "ssvcV203": [
      {
        "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
        "ssvcData": {
          "id": "CVE-2025-7693",
          "role": "CISA Coordinator",
          "options": [
            {
              "exploitation": "none"
            },
            {
              "automatable": "yes"
            },
            {
              "technicalImpact": "total"
            }
          ],
          "version": "2.0.3",
          "timestamp": "2025-08-18T18:05:26.945400Z"
        }
      }
    ],
    "cvssMetricV40": [
      {
        "type": "Secondary",
        "source": "PSIRT@rockwellautomation.com",
        "cvssData": {
          "Safety": "NOT_DEFINED",
          "version": "4.0",
          "Recovery": "NOT_DEFINED",
          "baseScore": 9.3,
          "Automatable": "NOT_DEFINED",
          "attackVector": "NETWORK",
          "baseSeverity": "CRITICAL",
          "valueDensity": "NOT_DEFINED",
          "vectorString": "CVSS:4.0/AV:N/AC:L/AT:N/PR:N/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
          "exploitMaturity": "NOT_DEFINED",
          "providerUrgency": "NOT_DEFINED",
          "userInteraction": "NONE",
          "attackComplexity": "LOW",
          "attackRequirements": "NONE",
          "privilegesRequired": "NONE",
          "subIntegrityImpact": "NONE",
          "vulnIntegrityImpact": "HIGH",
          "integrityRequirement": "NOT_DEFINED",
          "modifiedAttackVector": "NOT_DEFINED",
          "subAvailabilityImpact": "NONE",
          "vulnAvailabilityImpact": "HIGH",
          "availabilityRequirement": "NOT_DEFINED",
          "modifiedUserInteraction": "NOT_DEFINED",
          "modifiedAttackComplexity": "NOT_DEFINED",
          "subConfidentialityImpact": "NONE",
          "vulnConfidentialityImpact": "HIGH",
          "confidentialityRequirement": "NOT_DEFINED",
          "modifiedAttackRequirements": "NOT_DEFINED",
          "modifiedPrivilegesRequired": "NOT_DEFINED",
          "modifiedSubIntegrityImpact": "NOT_DEFINED",
          "modifiedVulnIntegrityImpact": "NOT_DEFINED",
          "vulnerabilityResponseEffort": "NOT_DEFINED",
          "modifiedSubAvailabilityImpact": "NOT_DEFINED",
          "modifiedVulnAvailabilityImpact": "NOT_DEFINED",
          "modifiedSubConfidentialityImpact": "NOT_DEFINED",
          "modifiedVulnConfidentialityImpact": "NOT_DEFINED"
        }
      }
    ]
  },
  "affected": [
    {
      "source": "PSIRT@rockwellautomation.com",
      "affectedData": [
        {
          "vendor": "Rockwell Automation",
          "product": "PLC - Micro850 L50E",
          "versions": [
            {
              "status": "affected",
              "version": "V20.011 - V22.011"
            }
          ],
          "defaultStatus": "unaffected"
        }
      ]
    }
  ],
  "published": "2025-08-18T18:15:40.573",
  "references": [
    {
      "url": "https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1736.html",
      "source": "PSIRT@rockwellautomation.com"
    }
  ],
  "vulnStatus": "Deferred",
  "weaknesses": [
    {
      "type": "Secondary",
      "source": "PSIRT@rockwellautomation.com",
      "description": [
        {
          "lang": "en",
          "value": "CWE-20"
        }
      ]
    }
  ],
  "descriptions": [
    {
      "lang": "en",
      "value": "A security issue exists due to improper handling of malformed CIP Forward Close packets during fuzzing. The controller enters a solid red Fault LED state and becomes unresponsive. Upon power cycle, the controller will enter recoverable fault where the MS LED and Fault LED become flashing red and reports fault code 0xF015. To recover, clear the fault."
    },
    {
      "lang": "es",
      "value": "Existe un problema de seguridad debido al manejo incorrecto de paquetes CIP Forward Close malformados durante el fuzzing. El controlador entra en un estado de fallo rojo fijo y deja de responder. Al reiniciar, el controlador entra en un fallo recuperable donde el LED MS y el LED de fallo parpadean en rojo e informan el código de fallo 0xF015. Para recuperarse, borre el fallo."
    }
  ],
  "lastModified": "2026-06-17T10:05:28.797",
  "sourceIdentifier": "PSIRT@rockwellautomation.com"
}