A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus TCP messages to port 502 using the Write Single Register function code (6).

Leer descripción completaMostrar menos

The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change. After this configuration change, the device will be in a denial-of-service state.

CVSS

Probabilidad de explotación (EPSS)

EPSS (Exploit Prediction Scoring System, de FIRST) estima la probabilidad de que una vulnerabilidad sea explotada en 30 días. Complementa a CVSS (impacto) y a CISA KEV (explotación confirmada).

🎯 Técnicas ATT&CK

Cómo se explota esta vulnerabilidad y qué consigue el atacante, en el lenguaje de MITRE ATT&CK.

Aplicación expuesta en red (AV:N, PR:N, UI:N) vulnerable a solicitudes Modbus TCP sin autenticación en puerto 502. El ataque provoca DoS mediante secuencia de mensajes que deshabilita el dispositivo.

Inferido por nuestro agente de análisis a partir de la descripción oficial, el vector CVSS y la CWE, y comprobado por un supervisor. Puede contener errores.

🛡️ Mitigaciones ATT&CK que cubren estas técnicas

Tecnologías afectadas (1)

CWE

Referencias

JSON original (NVD)

Mostrar
{
  "id": "CVE-2025-54848",
  "cveTags": [],
  "metrics": {
    "ssvcV203": [
      {
        "source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
        "ssvcData": {
          "id": "CVE-2025-54848",
          "role": "CISA Coordinator",
          "options": [
            {
              "exploitation": "none"
            },
            {
              "automatable": "no"
            },
            {
              "technicalImpact": "partial"
            }
          ],
          "version": "2.0.3",
          "timestamp": "2025-12-01T20:15:28.693110Z"
        }
      }
    ],
    "cvssMetricV31": [
      {
        "type": "Secondary",
        "source": "talos-cna@cisco.com",
        "cvssData": {
          "scope": "UNCHANGED",
          "version": "3.1",
          "baseScore": 7.5,
          "attackVector": "NETWORK",
          "baseSeverity": "HIGH",
          "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
          "integrityImpact": "NONE",
          "userInteraction": "NONE",
          "attackComplexity": "LOW",
          "availabilityImpact": "HIGH",
          "privilegesRequired": "NONE",
          "confidentialityImpact": "NONE"
        },
        "impactScore": 3.6,
        "exploitabilityScore": 3.9
      }
    ]
  },
  "affected": [
    {
      "source": "talos-cna@cisco.com",
      "affectedData": [
        {
          "vendor": "Socomec",
          "product": "DIRIS Digiware M-70",
          "versions": [
            {
              "status": "affected",
              "version": "1.6.9"
            }
          ]
        }
      ]
    }
  ],
  "published": "2025-12-01T16:15:53.723",
  "references": [
    {
      "url": "https://talosintelligence.com/vulnerability_reports/TALOS-2025-2248",
      "tags": [
        "Vendor Advisory"
      ],
      "source": "talos-cna@cisco.com"
    }
  ],
  "vulnStatus": "Analyzed",
  "weaknesses": [
    {
      "type": "Secondary",
      "source": "talos-cna@cisco.com",
      "description": [
        {
          "lang": "en",
          "value": "CWE-306"
        }
      ]
    }
  ],
  "descriptions": [
    {
      "lang": "en",
      "value": "A denial of service vulnerability exists in the Modbus TCP and Modbus RTU over TCP functionality of Socomec DIRIS Digiware M-70 1.6.9. A specially crafted series of network requests can lead to a denial of service. An attacker can send a sequence of unauthenticated packets to trigger this vulnerability.An attacker can trigger this denial-of-service condition by sending a sequence of Modbus TCP messages to port 502 using the Write Single Register function code (6). The attack sequence begins with a message to register 58112 with a value of 1000, indicating that a configuration change will follow. Next, a message is sent to register 29440 with a value corresponding to the new Modbus address to be configured. Finally, a message to register 57856 with a value of 161 commits the configuration change. After this configuration change, the device will be in a denial-of-service state."
    },
    {
      "lang": "es",
      "value": "Una vulnerabilidad de denegación de servicio existe en la funcionalidad Modbus TCP y Modbus RTU sobre TCP de Socomec DIRIS Digiware M-70 1.6.9. Una serie de solicitudes de red especialmente diseñadas puede conducir a una denegación de servicio. Un atacante puede enviar una secuencia de paquetes no autenticados para activar esta vulnerabilidad. Un atacante puede activar esta condición de denegación de servicio enviando una secuencia de mensajes Modbus TCP al puerto 502 utilizando el código de función Write Single Register (6). La secuencia de ataque comienza con un mensaje al registro 58112 con un valor de 1000, indicando que seguirá un cambio de configuración. A continuación, se envía un mensaje al registro 29440 con un valor correspondiente a la nueva dirección Modbus a configurar. Finalmente, un mensaje al registro 57856 con un valor de 161 confirma el cambio de configuración. Después de este cambio de configuración, el dispositivo estará en un estado de denegación de servicio."
    }
  ],
  "lastModified": "2026-09-26T00:10:00.127",
  "configurations": [
    {
      "nodes": [
        {
          "negate": false,
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:o:socomec:diris_digiware_m-70_firmware:1.6.9:*:*:*:*:*:*:*",
              "vulnerable": true,
              "matchCriteriaId": "741E83B6-F217-46E7-9E3A-8E446250C785"
            }
          ],
          "operator": "OR"
        },
        {
          "negate": false,
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:h:socomec:diris_digiware_m-70:-:*:*:*:*:*:*:*",
              "vulnerable": false,
              "matchCriteriaId": "76CAA8C6-29FD-40F3-9702-790CD73F3052"
            }
          ],
          "operator": "OR"
        }
      ],
      "operator": "AND"
    }
  ],
  "sourceIdentifier": "talos-cna@cisco.com"
}