CVE-2025-13911
Ignition by Inductive Automation, when installed with default OS service account settings, may expose the host system to an elevated code execution risk via the gateway backup restore functionality. An authenticated user with Gateway Administrator privileges can import a malicious gateway backup (.gwbk) file containing crafted project resources, scripts, or modules, resulting in code execution on the host system. This affects both Windows and Linux installations.
Leer descripción completaMostrar menos
On Windows, default installations often run the Ignition service as NT AUTHORITY\SYSTEM, resulting in code execution with full local system privileges. On Linux, default installations commonly run the Ignition service as root or with elevated privileges. Specific privilege level depends on installation configuration.
CVSS
- Versión: 4.0
- Vector: CVSS:4.0/AV:A/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
- Puntuación base: 7.3
Probabilidad de explotación (EPSS)
- Probabilidad de explotación en los próximos 30 días: 0.25%
- Percentil entre todas las CVEs puntuadas: 15
- Fecha de la puntuación: 6/10/2026
EPSS (Exploit Prediction Scoring System, de FIRST) estima la probabilidad de que una vulnerabilidad sea explotada en 30 días. Complementa a CVSS (impacto) y a CISA KEV (explotación confirmada).
🎯 Técnicas ATT&CK
Cómo se explota esta vulnerabilidad y qué consigue el atacante, en el lenguaje de MITRE ATT&CK.
- Explotación
T1210Exploitation of Remote Serviceslateral movement75 % - Impacto principal
T1068Exploitation for Privilege Escalationprivilege escalation85 % - Impacto secundario
T1059Command and Scripting Interpreterexecution80 %
Acceso a red adyacente (AV:A) con privilegios de Gateway Administrator (PR:H) en servicio remoto Ignition; restauración de backup malicioso ejecuta código con privilegios SYSTEM/root.
Inferido por nuestro agente de análisis a partir de la descripción oficial, el vector CVSS y la CWE, y comprobado por un supervisor. Puede contener errores.
🛡️ Mitigaciones ATT&CK que cubren estas técnicas
Tecnologías afectadas (1)
⚠ Inferidas por IA a partir de la descripción — NVD aún no ha analizado esta CVE; no son CPE verificados.
CWE
- CWE-250
Referencias
JSON original (NVD)
Mostrar
{
"id": "CVE-2025-13911",
"cveTags": [],
"metrics": {
"ssvcV203": [
{
"source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"ssvcData": {
"id": "CVE-2025-13911",
"role": "CISA Coordinator",
"options": [
{
"exploitation": "none"
},
{
"automatable": "no"
},
{
"technicalImpact": "total"
}
],
"version": "2.0.3",
"timestamp": "2025-12-18T20:44:32.471219Z"
}
}
],
"cvssMetricV31": [
{
"type": "Secondary",
"source": "ics-cert@hq.dhs.gov",
"cvssData": {
"scope": "UNCHANGED",
"version": "3.1",
"baseScore": 6.4,
"attackVector": "ADJACENT_NETWORK",
"baseSeverity": "MEDIUM",
"vectorString": "CVSS:3.1/AV:A/AC:H/PR:H/UI:N/S:U/C:H/I:H/A:H",
"integrityImpact": "HIGH",
"userInteraction": "NONE",
"attackComplexity": "HIGH",
"availabilityImpact": "HIGH",
"privilegesRequired": "HIGH",
"confidentialityImpact": "HIGH"
},
"impactScore": 5.9,
"exploitabilityScore": 0.5
}
],
"cvssMetricV40": [
{
"type": "Secondary",
"source": "ics-cert@hq.dhs.gov",
"cvssData": {
"Safety": "NOT_DEFINED",
"version": "4.0",
"Recovery": "NOT_DEFINED",
"baseScore": 7.3,
"Automatable": "NOT_DEFINED",
"attackVector": "ADJACENT",
"baseSeverity": "HIGH",
"valueDensity": "NOT_DEFINED",
"vectorString": "CVSS:4.0/AV:A/AC:H/AT:N/PR:H/UI:N/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
"exploitMaturity": "NOT_DEFINED",
"providerUrgency": "NOT_DEFINED",
"userInteraction": "NONE",
"attackComplexity": "HIGH",
"attackRequirements": "NONE",
"privilegesRequired": "HIGH",
"subIntegrityImpact": "NONE",
"vulnIntegrityImpact": "HIGH",
"integrityRequirement": "NOT_DEFINED",
"modifiedAttackVector": "NOT_DEFINED",
"subAvailabilityImpact": "NONE",
"vulnAvailabilityImpact": "HIGH",
"availabilityRequirement": "NOT_DEFINED",
"modifiedUserInteraction": "NOT_DEFINED",
"modifiedAttackComplexity": "NOT_DEFINED",
"subConfidentialityImpact": "NONE",
"vulnConfidentialityImpact": "HIGH",
"confidentialityRequirement": "NOT_DEFINED",
"modifiedAttackRequirements": "NOT_DEFINED",
"modifiedPrivilegesRequired": "NOT_DEFINED",
"modifiedSubIntegrityImpact": "NOT_DEFINED",
"modifiedVulnIntegrityImpact": "NOT_DEFINED",
"vulnerabilityResponseEffort": "NOT_DEFINED",
"modifiedSubAvailabilityImpact": "NOT_DEFINED",
"modifiedVulnAvailabilityImpact": "NOT_DEFINED",
"modifiedSubConfidentialityImpact": "NOT_DEFINED",
"modifiedVulnConfidentialityImpact": "NOT_DEFINED"
}
}
]
},
"affected": [
{
"source": "ics-cert@hq.dhs.gov",
"affectedData": [
{
"vendor": "Inductive Automation",
"product": "Ignition",
"versions": [
{
"status": "affected",
"version": "8.1.x"
},
{
"status": "affected",
"version": "8.3.x"
}
],
"defaultStatus": "unaffected"
}
]
}
],
"published": "2025-12-18T21:15:52.073",
"references": [
{
"url": "https://github.com/cisagov/CSAF/blob/develop/csaf_files/OT/white/2025/icsa-25-352-01.json",
"source": "ics-cert@hq.dhs.gov"
},
{
"url": "https://security.inductiveautomation.com/",
"source": "ics-cert@hq.dhs.gov"
},
{
"url": "https://www.cisa.gov/news-events/ics-advisories/icsa-25-352-01",
"source": "ics-cert@hq.dhs.gov"
}
],
"vulnStatus": "Deferred",
"weaknesses": [
{
"type": "Secondary",
"source": "ics-cert@hq.dhs.gov",
"description": [
{
"lang": "en",
"value": "CWE-250"
}
]
}
],
"descriptions": [
{
"lang": "en",
"value": "Ignition by Inductive Automation, when installed with default OS service\n account settings, may expose the host system to an elevated code \nexecution risk via the gateway backup restore functionality. An \nauthenticated user with Gateway Administrator privileges can import a \nmalicious gateway backup (.gwbk) file containing crafted project \nresources, scripts, or modules, resulting in code execution on the host \nsystem. This affects both Windows and Linux installations. On Windows, \ndefault installations often run the Ignition service as NT \nAUTHORITY\\SYSTEM, resulting in code execution with full local system \nprivileges. On Linux, default installations commonly run the Ignition \nservice as root or with elevated privileges. Specific privilege level \ndepends on installation configuration."
}
],
"lastModified": "2026-08-28T02:16:19.597",
"sourceIdentifier": "ics-cert@hq.dhs.gov"
}