CVE-2020-5801

High (7.5)—
Patch with priorityFIRST estimates a 30% chance of exploitation in the next 30 days. No confirmed active exploitation.
Severity7.5High · CVSS 3.1
Exploitation probability30 %higher than 99% of CVEs · score from Nov 25, 2026
Active exploitationNonot in the CISA catalog · checked Nov 25, 05:00 PM
Public exploitNot knownno public code found

An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected.

Timeline

Built from our own data: NVD, CISA KEV and other exploitation catalogues, FIRST EPSS, public exploits, specialised media and Orbitaley coverage.

  1. CVE record published in NVD
  2. Record last modified in NVD

Affected technologies (1)

NVD record

NVD status
Modified
Published
Dec 29, 2020
Last modified
Jun 17, 2026
CVSS vector
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
Weakness (CWE)
CWE-755

References

Raw JSON (NVD)

Show
{
  "id": "CVE-2020-5801",
  "cveTags": [],
  "metrics": {
    "cvssMetricV2": [
      {
        "type": "Primary",
        "source": "nvd@nist.gov",
        "cvssData": {
          "version": "2.0",
          "baseScore": 5,
          "accessVector": "NETWORK",
          "vectorString": "AV:N/AC:L/Au:N/C:N/I:N/A:P",
          "authentication": "NONE",
          "integrityImpact": "NONE",
          "accessComplexity": "LOW",
          "availabilityImpact": "PARTIAL",
          "confidentialityImpact": "NONE"
        },
        "acInsufInfo": false,
        "impactScore": 2.9,
        "baseSeverity": "MEDIUM",
        "obtainAllPrivilege": false,
        "exploitabilityScore": 10,
        "obtainUserPrivilege": false,
        "obtainOtherPrivilege": false,
        "userInteractionRequired": false
      }
    ],
    "cvssMetricV31": [
      {
        "type": "Primary",
        "source": "nvd@nist.gov",
        "cvssData": {
          "scope": "UNCHANGED",
          "version": "3.1",
          "baseScore": 7.5,
          "attackVector": "NETWORK",
          "baseSeverity": "HIGH",
          "vectorString": "CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H",
          "integrityImpact": "NONE",
          "userInteraction": "NONE",
          "attackComplexity": "LOW",
          "availabilityImpact": "HIGH",
          "privilegesRequired": "NONE",
          "confidentialityImpact": "NONE"
        },
        "impactScore": 3.6,
        "exploitabilityScore": 3.9
      }
    ]
  },
  "affected": [
    {
      "source": "vulnreport@tenable.com",
      "affectedData": [
        {
          "vendor": "n/a",
          "product": "Rockwell FactoryTalk Linx",
          "versions": [
            {
              "status": "affected",
              "version": "All versions of FactoryTalk Linx"
            }
          ]
        }
      ]
    }
  ],
  "published": "2020-12-29T16:15:14.730",
  "references": [
    {
      "url": "https://www.tenable.com/security/research/tra-2020-71",
      "tags": [
        "Third Party Advisory"
      ],
      "source": "vulnreport@tenable.com"
    },
    {
      "url": "https://www.tenable.com/security/research/tra-2020-71",
      "tags": [
        "Third Party Advisory"
      ],
      "source": "af854a3a-2127-422b-91ae-364da2661108"
    }
  ],
  "vulnStatus": "Modified",
  "weaknesses": [
    {
      "type": "Primary",
      "source": "nvd@nist.gov",
      "description": [
        {
          "lang": "en",
          "value": "CWE-755"
        }
      ]
    }
  ],
  "descriptions": [
    {
      "lang": "en",
      "value": "An attacker can craft and send an OpenNamespace message to port 4241 with valid session-id that triggers an unhandled exception in CFTLDManager::HandleRequest function in RnaDaSvr.dll, resulting in process termination. Observed in FactoryTalk Linx 6.11. All versions of FactoryTalk Linx are affected."
    },
    {
      "lang": "es",
      "value": "Un atacante puede crear y enviar un mensaje OpenNamespace al puerto 4241 con un ID de sesión válido que desencadena una excepción no controlada en la función CFTLDManager::HandleRequest en la biblioteca RnaDaSvr.dll, resultando en una terminación del proceso. Observado en FactoryTalk Linx versión 6.11. Todas las versiones de FactoryTalk Linx están afectadas"
    }
  ],
  "lastModified": "2026-06-17T03:22:15.710",
  "configurations": [
    {
      "nodes": [
        {
          "negate": false,
          "cpeMatch": [
            {
              "criteria": "cpe:2.3:a:rockwellautomation:factorytalk_linx:*:*:*:*:*:*:*:*",
              "vulnerable": true,
              "matchCriteriaId": "89622117-4485-4204-A5DA-B72F7F13D353",
              "versionEndIncluding": "6.11"
            }
          ],
          "operator": "OR"
        }
      ]
    }
  ],
  "sourceIdentifier": "vulnreport@tenable.com"
}