CVE-2011-20002
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.
CVSS
- Versión: 4.0
- Vector: CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
- Puntuación base: 8.3
Probabilidad de explotación (EPSS)
- Probabilidad de explotación en los próximos 30 días: 0.31%
- Percentil entre todas las CVEs puntuadas: 21
- Fecha de la puntuación: 1/10/2026
EPSS (Exploit Prediction Scoring System, de FIRST) estima la probabilidad de que una vulnerabilidad sea explotada en 30 días. Complementa a CVSS (impacto) y a CISA KEV (explotación confirmada).
Tecnologías afectadas (2)
⚠ Inferidas por IA a partir de la descripción — NVD aún no ha analizado esta CVE; no son CPE verificados.
CWE
- CWE-294
Referencias
JSON original (NVD)
Mostrar
{
"id": "CVE-2011-20002",
"cveTags": [],
"metrics": {
"ssvcV203": [
{
"source": "134c704f-9b21-4f2e-91b3-4a467353bcc0",
"ssvcData": {
"id": "CVE-2011-20002",
"role": "CISA Coordinator",
"options": [
{
"exploitation": "none"
},
{
"automatable": "no"
},
{
"technicalImpact": "partial"
}
],
"version": "2.0.3",
"timestamp": "2025-10-14T18:58:23.653672Z"
}
}
],
"cvssMetricV31": [
{
"type": "Secondary",
"source": "productcert@siemens.com",
"cvssData": {
"scope": "UNCHANGED",
"version": "3.1",
"baseScore": 7.4,
"attackVector": "NETWORK",
"baseSeverity": "HIGH",
"vectorString": "CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:H",
"integrityImpact": "HIGH",
"userInteraction": "NONE",
"attackComplexity": "HIGH",
"availabilityImpact": "HIGH",
"privilegesRequired": "NONE",
"confidentialityImpact": "NONE"
},
"impactScore": 5.2,
"exploitabilityScore": 2.2
}
],
"cvssMetricV40": [
{
"type": "Secondary",
"source": "productcert@siemens.com",
"cvssData": {
"Safety": "NOT_DEFINED",
"version": "4.0",
"Recovery": "NOT_DEFINED",
"baseScore": 8.3,
"Automatable": "NOT_DEFINED",
"attackVector": "NETWORK",
"baseSeverity": "HIGH",
"valueDensity": "NOT_DEFINED",
"vectorString": "CVSS:4.0/AV:N/AC:L/AT:P/PR:N/UI:N/VC:N/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X",
"exploitMaturity": "NOT_DEFINED",
"providerUrgency": "NOT_DEFINED",
"userInteraction": "NONE",
"attackComplexity": "LOW",
"attackRequirements": "PRESENT",
"privilegesRequired": "NONE",
"subIntegrityImpact": "NONE",
"vulnIntegrityImpact": "HIGH",
"integrityRequirement": "NOT_DEFINED",
"modifiedAttackVector": "NOT_DEFINED",
"subAvailabilityImpact": "NONE",
"vulnAvailabilityImpact": "HIGH",
"availabilityRequirement": "NOT_DEFINED",
"modifiedUserInteraction": "NOT_DEFINED",
"modifiedAttackComplexity": "NOT_DEFINED",
"subConfidentialityImpact": "NONE",
"vulnConfidentialityImpact": "NONE",
"confidentialityRequirement": "NOT_DEFINED",
"modifiedAttackRequirements": "NOT_DEFINED",
"modifiedPrivilegesRequired": "NOT_DEFINED",
"modifiedSubIntegrityImpact": "NOT_DEFINED",
"modifiedVulnIntegrityImpact": "NOT_DEFINED",
"vulnerabilityResponseEffort": "NOT_DEFINED",
"modifiedSubAvailabilityImpact": "NOT_DEFINED",
"modifiedVulnAvailabilityImpact": "NOT_DEFINED",
"modifiedSubConfidentialityImpact": "NOT_DEFINED",
"modifiedVulnConfidentialityImpact": "NOT_DEFINED"
}
}
]
},
"affected": [
{
"source": "productcert@siemens.com",
"affectedData": [
{
"vendor": "Siemens",
"product": "SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants)",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V2.0.2",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
},
{
"vendor": "Siemens",
"product": "SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants)",
"versions": [
{
"status": "affected",
"version": "0",
"lessThan": "V2.0.2",
"versionType": "custom"
}
],
"defaultStatus": "unknown"
}
]
}
],
"published": "2025-10-14T10:15:33.633",
"references": [
{
"url": "https://cert-portal.siemens.com/productcert/html/ssa-625789.html",
"source": "productcert@siemens.com"
}
],
"vulnStatus": "Deferred",
"weaknesses": [
{
"type": "Secondary",
"source": "productcert@siemens.com",
"description": [
{
"lang": "en",
"value": "CWE-294"
}
]
}
],
"descriptions": [
{
"lang": "en",
"value": "A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured."
}
],
"lastModified": "2026-06-16T23:30:34.700",
"sourceIdentifier": "productcert@siemens.com"
}