ModificadaCrítica (9.8)1.2%—GE Multilin B30 FirmwareGE Multilin B90 FirmwareGE Multilin C60 FirmwareGE Multilin C70 Firmware+1523/3/202217/6/2026
GE UR IED firmware versions prior to version 8.1x supports upgrading firmware using UR Setup configuration tool – Enervista UR Setup. This UR Setup tool validates the authenticity and integrity of firmware file before uploading the UR IED. An illegitimate user could upgrade firmware without appropriate privileges. The…
ModificadaCrítica (9.8)1.2%—GE Multilin B30 FirmwareGE Multilin B90 FirmwareGE Multilin C60 FirmwareGE Multilin C70 Firmware+1523/3/202217/6/2026
GE UR IED firmware versions prior to version 8.1x with “Basic” security variant does not allow the disabling of the “Factory Mode,” which is used for servicing the IED by a “Factory” user.
ModificadaMedia (5.3)0.88%—GE Multilin B30 FirmwareGE Multilin B90 FirmwareGE Multilin C60 FirmwareGE Multilin C70 Firmware+1523/3/202217/6/2026
GE UR firmware versions prior to version 8.1x shares MODBUS memory map as part of the communications guide. GE was made aware a “Last-key pressed” MODBUS register can be used to gain unauthorized information.
ModificadaAlta (7.5)0.67%—GE Multilin B30 FirmwareGE Multilin B90 FirmwareGE Multilin C60 FirmwareGE Multilin C70 Firmware+1523/3/202217/6/2026
GE UR firmware versions prior to version 8.1x web server interface is supported on UR over HTTP protocol. It allows sensitive information exposure without authentication.
ModificadaMedia (5.3)1.1%—GE Multilin B30 FirmwareGE Multilin B90 FirmwareGE Multilin C60 FirmwareGE Multilin C70 Firmware+1523/3/202217/6/2026
GE UR firmware versions prior to version 8.1x web server task does not properly handle receipt of unsupported HTTP verbs, resulting in the web server becoming temporarily unresponsive after receiving a series of unsupported HTTP requests. When unresponsive, the web server is inaccessible. By itself, this is not…
ModificadaMedia (6.1)0.61%—GE Multilin B30 FirmwareGE Multilin B90 FirmwareGE Multilin C60 FirmwareGE Multilin C70 Firmware+1523/3/202217/6/2026
GE UR firmware versions prior to version 8.1x supports web interface with read-only access. The device fails to properly validate user input, making it possible to perform cross-site scripting attacks, which may be used to send a malicious script. Also, UR Firmware web server does not perform HTML encoding of…