CVEEstadoSeveridadEPSS Explotación activaTecnologías afectadasPublicada ▼Modificada Descripción
ModificadaMedia (5.5)0.73%—Schneider-electric Modicon M221 Firmware11/12/202017/6/2026
A CWE-760: Use of a One-Way Hash with a Predictable Salt vulnerability exists in Modicon M221 (all references, all versions), that could allow an attacker to pre-compute the hash value using dictionary attack technique such as rainbow tables, effectively disabling the protection that an unpredictable salt would…
ModificadaMedia (4.3)0.53%—Schneider-electric Modicon M221 Firmware19/11/202017/6/2026
A CWE-200: Exposure of Sensitive Information to an Unauthorized Actor vulnerability exists in Modicon M221 (all references, all versions) that could allow non sensitive information disclosure when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.
ModificadaMedia (5.7)0.21%—Schneider-electric Modicon M221 Firmware19/11/202017/6/2026
A CWE-311: Missing Encryption of Sensitive Data vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to find the password hash when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller and broke the encryption keys.
ModificadaAlta (7.3)0.30%—Schneider-electric Modicon M221 Firmware19/11/202017/6/2026
A CWE-334: Small Space of Random Values vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption keys when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.
ModificadaAlta (7.3)0.30%—Schneider-electric Modicon M221 Firmware19/11/202017/6/2026
A CWE-326: Inadequate Encryption Strength vulnerability exists in Modicon M221 (all references, all versions) that could allow the attacker to break the encryption key when the attacker has captured the traffic between EcoStruxure Machine - Basic software and Modicon M221 controller.
ModificadaCrítica (9.8)1.6%—Schneider-electric Ecostruxure Machine ExpertSchneider-electric Somachine BasicSchneider-electric Modicon M100 FirmwareSchneider-electric Modicon M200 Firmware+122/4/202017/6/2026
A CWE-74: Improper Neutralization of Special Elements in Output Used by a Downstream Component ('Injection') vulnerability exists on EcoStruxure Machine Expert – Basic or SoMachine Basic programming software (versions in security notification). The result of this vulnerability, DLL substitution, could allow the…
ModificadaAlta (8.2)1.3%—Schneider-electric Modicon M100 FirmwareSchneider-electric Modicon M200 FirmwareSchneider-electric Modicon M221 FirmwareSchneider-electric ATV IMC Drive Controller Firmware+822/5/201917/6/2026
A CWE-306: Missing Authentication for Critical Function vulnerability exists which could cause a modification of device IP configuration (IP address, network mask and gateway IP address) when a specific Ethernet frame is received in all versions of: Modicon M100, Modicon M200, Modicon M221, ATV IMC drive controller,…
ModificadaMedia (5.3)1.3%—Schneider-electric Somachine BasicSchneider-electric Modicon M221 Firmware22/5/201917/6/2026
A Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause remote launch of SoMachine Basic when sending crafted ethernet message.
ModificadaMedia (5.5)0.31%—Schneider-electric Somachine BasicSchneider-electric Modicon M221 Firmware22/5/201917/6/2026
An Incorrect Default Permissions (CWE-276) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause unauthorized access to SoMachine Basic resource files when logged on the system hosting SoMachine Basic.
ModificadaAlta (7.5)1.1%—Schneider-electric Somachine BasicSchneider-electric Modicon M221 Firmware22/5/201917/6/2026
An Environment (CWE-2) vulnerability exists in SoMachine Basic, all versions, and Modicon M221(all references, all versions prior to firmware V1.10.0.0) which could cause cycle time impact when flooding the M221 ethernet interface while the Ethernet/IP adapter is activated.
ModificadaAlta (7.5)3.4%—ABB Pm554-tp-eth FirmwarePhoenixcontact ILC 151 ETH FirmwareSchneider-electric Modicon M221 FirmwareSiemens 6es7211-1ae40-0xb0 Firmware+617/4/201917/6/2026
ABB, Phoenix Contact, Schneider Electric, Siemens, WAGO - Programmable Logic Controllers, multiple versions. Researchers have found some controllers are susceptible to a denial-of-service attack due to a flood of network packets.
ModificadaAlta (7.5)1.1%—Schneider-electric Modicon M221 Firmware29/8/201817/6/2026
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to decode the password using rainbow table.
ModificadaCrítica (9.8)1.9%—Schneider-electric Modicon M221 Firmware29/8/201817/6/2026
A Permissions, Privileges, and Access Control vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to overwrite the original password with their password. If an attacker exploits this vulnerability and…
ModificadaCrítica (9.8)2.5%—Schneider-electric Modicon M221 Firmware29/8/201817/6/2026
An Information Management Error vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to replay authentication sequences. If an attacker exploits this vulnerability and connects to a Modicon M221, the…
ModificadaAlta (7.5)2.8%—Schneider-electric Modicon M221 Firmware29/8/201817/6/2026
An Improper Check for Unusual or Exceptional Conditions vulnerability exists in Schneider Electric's Modicon M221 product (all references, all versions prior to firmware V1.6.2.0). The vulnerability allows unauthorized users to remotely reboot Modicon M221 using crafted programing protocol frames.
ModificadaMedia (6.5)2.1%—Schneider-electric Modicon M241 FirmwareSchneider-electric Modicon M251 FirmwareSchneider-electric Modicon M221 Firmware30/6/201717/6/2026
A predictable value range from previous values issue was discovered in Schneider Electric Modicon PLCs Modicon M221, firmware versions prior to Version 1.5.0.0, Modicon M241, firmware versions prior to Version 4.0.5.11, and Modicon M251, firmware versions prior to Version 4.0.5.11. The affected products generate…