Vulnerabilidades

Resumen — últimos 7 días

Vulnerabilidades nuevas2989▼ 73 respecto a la semana anterior
Críticas / altas1415▲ 65 respecto a la semana anterior
Nueva explotación activa (KEV)4▼ 5 respecto a la semana anterior
Sin puntuar (sin CVSS)382▼ 128 respecto a la semana anterior
–

16 resultados, ordenados por fecha de publicación (más recientes primero)

CVEEstadoSeveridadEPSS Explotación activaTecnologías afectadasPublicada ▼Modificada Descripción
ModificadaMedia (5.3)0.43%—Siemens Logo! 8 BM FirmwareSiemens Logo!8 BM Fs-05 Firmware11/10/202217/6/2026
A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA1) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA1) (All versions), LOGO! 24CEo…
ModificadaAlta (7.5)0.94%—Siemens Logo! 8 BM FirmwareSiemens Logo!8 BM Fs-05 Firmware11/10/202217/6/2026
A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions), LOGO! 12/24RCE (6ED1052-1MD08-0BA2) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA2) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions), LOGO! 230RCE…
ModificadaCrítica (9.8)0.98%—Siemens Logo! 8 BM FirmwareSiemens Logo!8 BM Fs-05 Firmware11/10/202217/6/2026
A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA1) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA1) (All versions), LOGO! 24CEo…
ModificadaAlta (7.5)0.28%—Siemens Logo! 8 BM FirmwareSiemens Logo!8 BM Fs-05 Firmware11/10/202217/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Affected devices load firmware updates without checking the authenticity. Furthermore the integrity of the unencrypted firmware is only verified by a non-cryptographic method. This could allow an attacker to manipulate a…
ModificadaMedia (5.5)0.27%—Siemens Logo! 8 BM Firmware15/3/202117/6/2026
A vulnerability has been identified in LOGO! 12/24RCE (6ED1052-1MD08-0BA1) (All versions), LOGO! 12/24RCEo (6ED1052-2MD08-0BA1) (All versions), LOGO! 230RCE (6ED1052-1FB08-0BA1) (All versions), LOGO! 230RCEo (6ED1052-2FB08-0BA1) (All versions), LOGO! 24CE (6ED1052-1CC08-0BA1) (All versions), LOGO! 24CEo…
ModificadaAlta (7.5)1.4%—Siemens Logo! 8 BM Firmware14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). The password used for authentication for the LOGO! Website and the LOGO! Access Tool is sent in a recoverable format. An attacker with access to the network traffic could derive valid logins.
ModificadaAlta (7.7)0.32%—Siemens Logo! 8 BM Firmware14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3), LOGO! Soft Comfort (All versions < V8.3). The LOGO! program files generated and used by the affected components offer the possibility to save user-defined functions (UDF) in a password protected way. This protection is…
ModificadaMedia (5.5)0.20%—Siemens Logo! 8 BM Firmware14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). The firmware update of affected devices contains the private RSA key that is used as a basis for encryption of communication with the device.
ModificadaAlta (7.5)0.82%—Siemens Logo! 8 BM Firmware14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Due to the usage of an insecure random number generation function and a deprecated cryptographic function, an attacker could extract the key that is used when communicating with an affected device on port 8080/tcp.
ModificadaMedia (5.5)0.18%—Siemens Logo! 8 BM FirmwareSiemens Logo! Soft Comfort14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3), LOGO! Soft Comfort (All versions < V8.3). The encryption of program data for the affected devices uses a static key. An attacker could use this key to extract confidential information from protected program files.
ModificadaAlta (7.5)0.50%—Siemens Logo! 8 BM Firmware14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). Due to the usage of an outdated cipher mode on port 10005/tcp, an attacker could extract the encryption key from a captured communication with the device.
ModificadaAlta (7.5)0.65%—Siemens Logo! 8 BM Firmware14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). The implemented encryption for communication with affected devices is prone to replay attacks due to the usage of a static key. An attacker could change the password or change the configuration on any affected device if…
ModificadaCrítica (9.8)1.6%—Siemens Logo! 8 BM Firmware14/12/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). A service available on port 10005/tcp of the affected devices could allow complete access to all services without authorization. An attacker could gain full control over an affected device, if he has access to this…
ModificadaCrítica (9.8)8.7%—Siemens Logo! 8 BM Firmware14/7/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (V1.81.01 - V1.81.03), LOGO! 8 BM (incl. SIPLUS variants) (V1.82.01), LOGO! 8 BM (incl. SIPLUS variants) (V1.82.02). A buffer overflow vulnerability exists in the Web Server functionality of the device. A remote unauthenticated attacker could…
ModificadaCrítica (9.1)2.0%—Siemens Logo! 8 BM Firmware10/6/202017/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions). The vulnerability could lead to an attacker reading and modifying the device configuration and obtain project files from affected devices. The security vulnerability could be exploited by an unauthenticated attacker with network…
ModificadaAlta (7.4)1.1%—Siemens Logo! 8 BM Firmware30/8/201717/6/2026
A vulnerability has been identified in LOGO! 8 BM (incl. SIPLUS variants) (All versions < V8.3). An attacker who performs a Man-in-the-Middle attack between the LOGO! BM and other devices could potentially decrypt and modify network traffic.