Vulnerabilidades

Resumen — últimos 7 días

Vulnerabilidades nuevas2904▼ 176 respecto a la semana anterior
Críticas / altas1294▼ 55 respecto a la semana anterior
Nueva explotación activa (KEV)5▼ 3 respecto a la semana anterior
Sin puntuar (sin CVSS)487▼ 22 respecto a la semana anterior
–

9 resultados, ordenados por fecha de publicación (más recientes primero)

CVEEstadoSeveridadEPSS Explotación activaTecnologías afectadasPublicada ▼Modificada Descripción
AnalizadaAlta (8.7)0.64%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP and CIP grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
AnalizadaAlta (8.7)0.48%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive grammar tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
AnalizadaAlta (8.7)0.39%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. This vulnerability is triggered during fuzzing of multiple CIP classes, which causes the CIP port to become unresponsive.
AnalizadaAlta (8.7)0.60%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limits Storms tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
AnalizadaAlta (8.7)0.60%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive limited storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
AnalizadaAlta (8.7)0.60%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles Comprehensive step limit storm tests, the device reboots
AnalizadaAlta (8.7)0.48%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. Fuzzing performed using Defensics causes the device to become unresponsive, requiring a reboot.
AnalizadaAlta (8.7)0.60%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. During execution of the Achilles EtherNet/IP Step Limit Storm tests, the device reboots unexpectedly, causing the Link State Monitor to go down for several seconds.
AnalizadaAlta (8.7)0.48%—Rockwellautomation Armorstart LT Firmware20/1/202617/6/2026
A security issue exists within ArmorStart® LT that can result in a denial-of-service condition. After running a Burp Suite active scan, the device loses ICMP connectivity, causing the web application to become inaccessible.