Vulnerabilidades

Resumen — últimos 7 días

Vulnerabilidades nuevas3006▼ 69 respecto a la semana anterior
Críticas / altas1420▲ 54 respecto a la semana anterior
Nueva explotación activa (KEV)4▼ 5 respecto a la semana anterior
Sin puntuar (sin CVSS)382▼ 128 respecto a la semana anterior
–

57 resultados, ordenados por fecha de publicación (más recientes primero)

CVEEstadoSeveridadEPSS Explotación activaTecnologías afectadasPublicada ▼Modificada Descripción
ModificadaAlta (7.8)2.5%—Schneider-electric Interactive Graphical Scada System19/11/202017/6/2026
A CWE-119 Improper Restriction of Operations within the Bounds of a Memory Buffer vulnerability exists in IGSS Definition (Def.exe) version 14.0.0.20247 and prior that could cause Remote Code Execution when malicious CGF (Configuration Group File) file is imported to IGSS Definition.
ModificadaAlta (7.8)0.51%—Schneider-electric Interactive Graphical Scada System23/3/202017/6/2026
A CWE-306: Missing Authentication for Critical Function vulnerability exists in IGSS (Versions 14 and prior using the service: IGSSupdate), which could allow a local user to execute processes that otherwise require escalation privileges when sending local network commands to the IGSS Update Service.
ModificadaAlta (7.5)4.1%—Schneider-electric Interactive Graphical Scada System23/3/202017/6/2026
A CWE-22: Improper Limitation of a Pathname to a Restricted Directory exists in IGSS (Versions 14 and prior using the service: IGSSupdate), which could allow a remote unauthenticated attacker to read arbitrary files from the IGSS server PC on an unrestricted or shared network when the IGSS Update Service is enabled.
ModificadaAlta (7.8)1.3%—Schneider-electric Interactive Graphical Scada System15/7/201917/6/2026
A CWE-787: Out-of-bounds Write vulnerability exists in Interactive Graphical SCADA System (IGSS), Version 14 and prior, which could cause a software crash when data in the mdb database is manipulated.
ModificadaAlta (7.8)0.38%—Schneider-electric Interactive Graphical Scada System12/2/201817/6/2026
A security misconfiguration vulnerability exists in Schneider Electric's IGSS SCADA Software versions 12 and prior. Security configuration settings such as Address Space Layout Randomization (ASLR) and Data Execution prevention (DEP) were not properly configured resulting in weak security.
ModificadaAlta (7.8)1.3%—Schneider-electric Interactive Graphical Scada System7/4/201717/6/2026
A DLL Hijacking issue was discovered in Schneider Electric Interactive Graphical SCADA System (IGSS) Software, Version 12 and previous versions. The software will execute a malicious file if it is named the same as a legitimate file and placed in a location that is earlier in the search path.
ModificadaAlta (10)21%—Schneider-electric Interactive Graphical Scada System21/1/201316/6/2026
Stack-based buffer overflow in Schneider Electric Interactive Graphical SCADA System (IGSS) 10 and earlier allows remote attackers to execute arbitrary code by sending TCP port-12397 data that does not comply with a protocol.